Description
Addressable monitor module of 2 conventional zones, allows the connection of up to 20 conventional detectors and / or 32 conventional manual call points per zone. Can identify between detector alarm and push button, between the fault by cutting or by short circuit in the zone. It takes two loop addresses. Requires 24 Vdc auxiliary power. LED status indicator. Connection through removable strips up to 2.5mm2 section. Possibility of being installed in DIN rail or flat to wall mounting in box BOX-ONE. Consumption less than 300μA at rest. Allows installation without polarity. Red color. Dimensions: 100 x 82 x 23 mm. CPR certificate EN54-18.